How it works: how Nem adom el controls the water heater and the car

Under gross settlement fed-in power earns about 5 Ft/kWh while bought power costs 36–70 Ft/kWh, so Nem adom el sends the surplus into the water heater and the car. It decides as you would if you watched the meter all day: every 30 seconds it looks at how much you sell or buy, and switches by that. Here are the exact rules, with the real numbers.

What switches the water heater?

A Shelly relay that switches the heater's power on and off. The heater's own thermostat stays in place and still decides when the water is hot enough; we only decide when it may get power.

When does the water heater switch on?

  1. When the sun covers all of it: over 3 minutes you sell about 90% of the heater's power on average. The heater then heats practically for free.
  2. When the sun covers only part of it (say 500 W on a dull day): the water has to be heated today anyway, and the missing power costs the same now as in the afternoon. So it heats in the sunniest hours left, to get as much sun into the water as it can. On a weak morning it waits, because noon brings more sun; in the afternoon it does not wait, because nothing better is coming. Condition: at least 300 W of surplus over 5 minutes.
  3. Backup: if the water is not hot yet, it heats from the grid from an hour and a half before sunset (but by 18:00 at the latest) until the thermostat stops it. Sunset is worked out for every day, so it comes earlier in winter and later in summer: about 14:50 in early November, before half past two in mid-December, 18:00 in summer. In summer the afternoon sun still gets its chance; in winter we do not wait for the dark. There is always hot water in the evening.
  4. Hot water at night too (a setting on the dashboard, on by default): from the backup time until sunrise the heater stays on and its own thermostat keeps the water warm, so there is hot water in the evening and in the morning. A smaller heater needs this, as the evening baths use its water up. With a big one (say 150 litres) you can turn it off: water heated by day is still warm in the morning, and nothing heats from the grid at night. Keeping it warm from midnight to sunrise does not count as the day's heating, so the next afternoon's backup still comes.

It learns how many hours of heating your water takes, from the days the thermostat stopped the heater, and picks the sunniest hours from one and a half times that, because the weather can turn.

Does it not switch the heater too often?

  • It decides on averages: 3–5 minutes before switching on, 3 minutes before switching off, so a passing cloud does not switch it off.
  • At least 5 minutes pass between two switchings.
  • Heating on the sun, it only switches off when you buy more than 300 W on average; on part of its power from the sun, when the sun reaching the heater falls below 150 W.
  • A backup heating started in the afternoon goes on until the water is hot.
  • The water is hot when the thermostat stops the heater (it draws under 50 W for 5 minutes). In sunshine the Shelly stays on after that, so when the water cools a little the thermostat tops it up from the sun. Only with a switch that measures nothing (Shelly Pro 1) do we count the water hot after 3 hours of heating a day.

So it typically switches a few times a day; the heater's own thermostat switches more often than that.

What if my solar system is three-phase?

A three-phase inverter spreads its output evenly over the three phases, while the heater is mostly on one, so only a third of the surplus reaches the heater's phase. If the meter counts each phase on its own, the heater then buys on its phase while the home as a whole sells. So for heating fully on the sun the control waits for about three times the surplus (about 5.4 kW of selling for a 2 kW heater), and with less it heats only in the sunniest hours. You can set on the Account page whether your solar system and heater are one- or three-phase; until you do, we assume a three-phase system above 5 kWp and a one-phase heater.

How does it charge the car?

The charger connects to us over the standard OCPP protocol, and we set amp by amp how much current it may give. The charger tells the car with a PWM signal, the standard language of every charger and car. We never stop the charge, we only set its speed.

  • A plugged-in car always charges, by day at least on the smallest current (6 A: about 1.4 kW for a one-phase car, 4.1 kW for a three-phase one). What the sun does not cover comes from the grid: the car takes that power some time anyway.
  • In sunshine the charge follows the surplus, by the last minute's average: up at once to the highest current that buys at most about 500 W; down only when you buy more than 650 W, so it does not hunt around the edge.
  • A sudden large load (buying over 1500 W, say a kettle) lowers the current at once, without waiting for the average.
  • From sunset to sunrise it charges at full power: there is no sun to follow, so we lift our limit and the charger gives its own maximum (set by the electrician for your fuses). In the morning it starts again from 6 A and follows the sun.
  • With the "Charge now" button it charges at full power by day too, until you unplug the car.
  • It recognises from the charging power whether your car charges on one phase or three.

Who comes first: the water heater or the car?

The heater, because hot water is needed every day and the car can wait. What the car takes from the sun above its smallest current is the heater's for the asking; once the heater is on, the car charges on what is left (at least 6 A). At night the car gives nothing to the heater.

What happens if something fails or I step in?

  • Switching by hand always wins: we never switch off what we did not switch on. If you switch ours off in the Shelly app or at the switch, we leave it alone for 3 hours. The dashboard has "Heat now" and "Switch off" buttons too.
  • If our server or the internet goes down, you still have hot water: the heater goes back to its own thermostat, as if we were not there. If it is heating, it stays on until the thermostat stops it. If we are holding it off, that goes to the Shelly with a 3-hour timer, which we renew every half hour; if we go silent, the Shelly switches it back on by itself within 3 hours at most. The heater may then heat from the grid, as it would without us. After a power cut the Shelly starts switched on (we set this on it when it connects), because its timer is lost in the power cut. As soon as we reach it again, we take control back. The charger's limit lasts 15 minutes; after that the charger charges at its own full power.
  • If only the grid meter goes quiet (the Shelly Pro 3EM sends nothing): a heater already on the sun stays on until its thermostat stops it, because hot water by the evening comes first. Nothing new is switched on from the sun then, but the backup heating before sunset still comes.
  • A restart forgets nothing: the learned heater power, the daily need and today's heating are saved.

How does the calculator count?

  • It models an average year hour by hour: 12 months × 3 kinds of weather (35% sunny, 35% middling, 30% grey days) × car at home or away × 24 hours. One average day a month would overstate how much surplus the heater can take, because the surplus comes in big lumps on sunny days and not at all on grey ones.
  • Production: about 1040 kWh per kWp a year, facing south. Low on purpose, checked against a real 8 kW system near Budapest in 2025–2026.
  • Hot water: 1.2 kWh per person a day plus 0.8 kWh of the tank's standing loss. If there is a battery, the inverter fills it first, as it does today.
  • With a three-phase system and a one-phase heater it counts only a third of the surplus for the heater.
  • The promise is 80% of the modelled saving, rounded down to a thousand forints: better to promise less.

Why is the water heater not controlled steplessly (PWM)?

We looked into it. Certified stepless heater controllers exist, and we could drive the my-PV AC•THOR, for one. Fitted, though, they cost about 270–340 thousand Ft and, by our estimate, bring about 5–20 thousand Ft a year more than a relay: many years to pay back. Cheap home-made controllers are no answer: phase-angle control of a 2 kW element goes past the standard's (EN 61000-3-2) harmonic limit, and switching whole cycles on and off (burst firing) may be counted by a smart meter as separate buying and selling. When a certified controller gets cheaper, we will look again.

All the numbers in one place

How often it decides every 30 seconds
Heater on, full sun 90% of the heater's power sold over 3 minutes
Heater on, part sun ≥300 W of surplus over 5 minutes, in the sunniest hours left
Heater off >300 W bought over 3 minutes; on part sun, the sun reaching the heater <150 W
Between two switchings at least 5 minutes
Backup heating starts between an hour and a half before sunset (18:00 at the latest) and 21:00, until the thermostat stops it
"The water is hot" under 50 W for 5 minutes; with a switch that measures nothing, 3 hours of heating a day
After switching off by hand left alone for 3 hours
Hot water at night too on from the backup time until sunrise, the thermostat decides (on by default, can be turned off)
If we go silent the heater is its thermostat's within 3 hours at most (the off timer renewed every half hour)
Car, smallest current 6 A (about 1.4 kW on one phase, 4.1 kW on three)
Car, current up at once, up to 500 W bought (1-minute average)
Car, current down above 650 W bought; above 1500 W at once
Car at night full power from sunset to sunrise
Calculator's promise 80% of the modelled saving
This describes the control as it works in November 2026. If you have a question or think something would work better another way, write to info@nemadomel.hu.

Our other sitesAjánlAI – AI visibility report for local businesses: whether the AI assistants recommend you, who they recommend instead, and what to fix.TáborNavigátor – Children's camps in one place: a camp finder by location, age, price and category (in Hungarian). Barion, Mastercard, Visa, Apple Pay, Google Pay